504   Calculation Type - RMS or peak...

This tissue has following status: green

Proposer: Christoph Brunner , UTInnovation

Page: 18

Clause: 5.5.3

Paragraph:

Category: Issue for edition 2 of this part

Issue: According to the proposed solution for TISSUE 270 from 7-3, a data ClcTyp shall be added to the common logical node. That data shall indicate, wthere RMS values or other calculation methods are used in a specific logical node instance

Proposal: Add data ClcTyp of CDC INT as described in the TISSUE resolution for TISSUE 270

Discussion Created Status
?
Ballot until Editor
Ballot time is finished 24 May 07 green Siemens AG
Henry Dawidczak
The max amplitude should be peak amplitude 20 Apr 07 final proposal 20.5.2007 Editors Group
The new data should be optional. So I suggest to insert it into each LN where may mag/ang occur. 18 Apr 07 red Siemens AG
Henry Dawidczak
In principle agreed. 16 Apr 07 red Siemens AG
Henry Dawidczak