354 There is no SCL configuration feedback that reflect local changes.
If you want to see other tissues for this part. This tissue has following status: blue Proposer: Herb Falk , SISCONET Page: 19 Clause: 7 Paragraph: Category: Issue for edition 2 of this part Issue: The general flow of SCL information is a ICD (can be generated by the IED vendor's tool) is provided to a system configuration tool. This tool, in turn, generates an SSD or SCD file. The SCD file can be compressed for exchange to the IED vendor's tool as a CID. The IED vendor's tool then reconfigures the IED.
Proposal: This capability needs to be fully specified with the appropriate schema modification to allow IED vendor tools to export a revised CID.
|