321   Use of TVTR,TCTR

This tissue has following status: blue

Proposer: Henry Dawidczak , Siemens AG

Page: 60,61

Clause: 5.13

Paragraph:

Category: Issue for edition 2 of this part

Issue: The LN TCTR and TVTR contain data of type sampled value which are mandatory. It is possible to implement the LN TCTR and TVTR in an IED without providing services for sampled values. If yes, you could use the EEHealth to model a information or a state of an external instrument transformer.

Proposal:

Discussion Created Status
?
Ballot until Editor
The issue to have Amp or Vol conditional mandatory is already discussed in TISSSUE 80 and already solved in IEC 61850-7-4, Amd 2 CD. 10 May 06 blue UTInnovation
Christoph Brunner